ECO-24 | ||
---|---|---|
|
Click for Datasheet Click for Installation & Operation Instructions Click for Product Brochure Click for Commissioning Form (Interactive) Click for Commissioning Form (Printable) |
EcoLeak Eco-24
A multi-zone control panel for water and refrigerant gas leak detection
This is the latest addition to the EcoLeak range of leak detection panels
The EcoLeak ECO-24 panel is a multi-zone control panel for water and refrigerant gas leak detection and is an extension of the existing ECO-1 and ECO-6 panels.
All three of the EcoLeak panels are suitable for use in small and medium sized areas within residential or commercial buildings to provide cost-effective leak detection.
ECO-24 is 24-zone panel which can monitor up to 24 EcoLeak water sensing cable, mini probes or AquiTron AT-SRG Refrigerant gas sensors.
The 24 zones are split into four channels of six zones. This allows independent control of four areas as each channel has its own set of volt-free relays for control of auxiliary equipment such as BMS, remote alarms, solenoid valves or refrigerant pump down.
The ECO-24 panel is ideally suited to provide centralised monitoring for smaller AT-SRG refrigerant leak detection systems. The compact panel is perfectly suited for installation within reception or security areas, providing fast, effective and sensor-specific alarms for immediate response.
5-year warranty
The Aquilar products now come with a 5-year warranty for total peace of mind.
TECHNICAL INFORMATION | |
---|---|
Sensing cable compatibility | EcoLeak sensing cable (1m to 30m) |
Detection probes | EcoLeak Probes |
Refrigerant sensor | Refrigerant gas probe AT-SRG |
Maximum sensing circuit | 30 metres sensing cable per zone or 1 x EcoLeak Probe per zone or 1 x AT-SRG refrigerant sensor per zone |
Maximum jumper/leader cable length | 300 meters per zone |
Number of zones | 24 (4 channels of 6) |
Sensing circuit | 2 wire sensing |
Network capabilities | ECO-24 panel can monitor up to 24 no ECO-24 panels via ECO-NET |
Enclosure | Powder coated steel, colour RAL 9016 Matt white, lockable |
Cable entries | 26No 20mm, 8No 25mm |
Dimension and weight | 315 x 270 x 100mm W x H x D, 3.5Kg |
Working temperature | 5°C to 40°C non-condensing |
Humidity | 5% to 95% non-condensing |
Power supply | 230/120Vac, 50/60Hz,12Vdc, 6 watts |
Audible alarm | 90db at 10cm |
Relay output | Number: 12 Total 4 x Channel relays for Leak 4 x Channel relays for Fault 2 x common Leak 1 x common fault 1 x common for remote Sounder (leak or fault) Type SPDT, Rated at 3A at 250Vac / 24Vdc |
Status LED | Power (Mains-Green), Leak (Red), Fault (Yellow) |
Battery backup | Optional separate unit, providing up to 24 hour, AT-PSU-12-3 + AT-BAT |